Level and Flow navigation Level and Flow Online Sales home New Flowline products Level and Flow Online Sales store Flowline part numbers Contact Level and Flow Online Sales Level and Flow Online Sales Extra Links Level and Flow Online Sales home Level and Flow Online Sales store Contact Level and Flow Online Sales Level and Flow Online Sales home Level and Flow Online Sales store

Switch-Pak with Compact Junction Box

Switch-Pak™ with Compact Junction Box

-Data Sheet-
-Manual-

AU15
AV16
AZ18

 

Offered in CSA and Cenelec approved intrinsically safe or general purpose configurations, this Switch-Pak high level spill prevention switch package provides a fixed level switch point with a 1A relay or dry contact closure interface for remote devices such as a PLC, SCADA or alarm. The product is typically selected for pressurized and/or highly corrosive bulk storage, day tank and waste sump applications. This product is completely compatible with all Flowline relote relay controllersand alarms.

 

-Specifications-

Length: 6" to 10' (15 cm to 3m) -ULTRASONIC (AU15)-
Switch point: 1 (set by factory) Supply voltage: 12-36 VDC
Orientation: ± 30° vertical Consumption: 25 mA maximum
Process temp: F: -40° to 194°
C: -40° to 90°
Contact type: (1) SPST relay
Contact rating: GP: 120 VAC/VDC @ 1A
IS: 32 VDC @ 0.5A
Pressure: AU1_: 150 psi (10 bar)
AZ1_: 150 psi (10 bar)
AV1_: 25 psi (1.7 bar)

Contact output:

Selectable NO/NC
Classification: Intrinsically safe
Wetted material: 424_: PP
524_: PVDF Kynar
-VIBRATION (AZ18)-
Supply voltage: 12-36 VDC
Process mount: _243: 2" NPT
_247: 1 1/2" G
Consumption: 25 mA maximum
Contact type: (1) SPST relay
Enclosure rating: NEMA 4X (IP65) Contact rating: 120 VAC/VDC @ 1A
Installed height: 3.6" (9.1 cm) above tank process mount Contact output: Selectable NO/NC
Classification: General purpose
Enclosure material: PP, UL94VO -BUOYANCY (AV16)-
Conduit entrance: Single, 1/2" NPT Contact type: (1) SPDT reed
Termination: 2-4 poles Contact rating: 120 VAC/VDC @ 15 VA
CE compliance: EN 50082-2 immunity
EN 55011 emission
EN 61010-1 safety
Contact output: Selectable NO/NC
Classification: General purpose

Call toll-free: 888.206.4108--- Email: sales@levelandflowonlinesales.com --- Fax: 636.537.1405